Perencanaan Jalur Perpipaan Fire Fighting Foam Pada Bangunan Pump Room Filling Station On The Spot Tahap 1 Terminal Mirah Surabaya

  • Moh Warits Dwi Riski Politeknik Perkapalan Negeri Surabaya
  • Mardi Santoso Politeknik Perkapalan Negeri Surabaya
  • Sudiyono Sudiyono Politeknik Perkapalan Negeri Surabaya
Keywords: Pump Head, Proportioner, Pipe Flow Expert

Abstract

State-owned enterprises enganged in logistics in the fields of gas, fuel oil, and waste
treatment develop developments in the distribution of fuel oil. The need for foam fire fighting
installation in the pump room buildings with a handled area of 17 m x 10 m to prevent a fire occurs by
fuel oil and adjusting the MSDS of the fuel handled, namely MFO (Marine Fuel Oil) and HSD (High
Speed Diesel). Then perform calculations starting from the calculation of the headloss, pump head,
pump power, the amount of water and foam concentrate needed, modelling analysis with help of pipe
flow expert software in order to make comparisons with the calculations carried out and estimate the
cost of material needed. The area handled is 170 m2 . The total headloss obtained is 50,308 m and the
pump power is 17,48 kW. The minimum amount of water needs is 10.718,5 litres and a minimum foam
concentrate needs is 331,5 litres. The estimated value of material costs is Rp. 956.860.882,3-.

Published
2022-02-12