Analisa Kebutuhan Air Pada Hydrant Dan Sprinkler Di Gedung VPSA

  • Muhammad Tsabitul Azmi Politeknik Perkapalan Negeri Surabaya
  • Ekky Nur Budiyanto Politeknik Perkapalan Negeri Surabaya
  • Ni’matut Tamimah Politeknik Perkapalan Negeri Surabaya
Keywords: Hydrant indoor, Sprinkler, SNI, NFPA

Abstract

The VPSA Building is an office located in surabaya, East Java, which has recently been
constructed and does not yet have fire protection. Therefore, the installation of a fire fighting system
is necessary to prevent fire hazard in accordance with SNI. The calculations carried out include
analysis of waterrequirements in the sprinkler and hydrant indoor as well as tank capacity for water
distribution. From the results of the analysis, data was obtained sprinkler 15750 liter, hydrant indoor
72000. So the total water calculation for hydrant and sprikler system is 87.75 ????????
, and tank capacity
requirements for hydrant and sprinkler in the VPSA building is 100 ????????.

Published
2024-11-17