Perancangan Sistem Perpipaan Air Bersih Gedung Perkantoran 6 Lantai
Abstract
Every building development usually has a problem in managing the clean water system, so
the plumbing system becomes an important solution for each building. This research aims to design a
plumbing system in a multi-storey building. This design refers to the SNI 8153: 2015 standard
regarding plumbing systems in buildings. The distribution of clean water is carried out through a
ground water tank and pumped into a clean water pipeline to each sanitary unit. The method used is
to determine the flow rate based on 252 people. The results of the calculation of the average clean
water demand for one day is 30240 liters / day with a peak demand of 220.5 liters / minute. The
minimum ground water tank capacity required is 10.08 m3. The total pump head that occurs in this
system is 26.374 meters and the pump power required to supply water is 0.272 kWatt.