PERENCANAAN FIRE FIGHTING MENGGUNAKAN FLUIDA AIR DAN BUSA DI GEDUNG CPC PERUSAHAAN MINYAK NABATI
Abstract
Abstract - The Gresik Crude Palm Oil industrial company stores the production of Crude Palm Oil in Shelves measuring 8 x 4 x 4 m with a volume of 128 m3. The need for a fire extinguisher installation in the form of foam chamber in the form of foam fluid by adjusting MSDS Crude Palm Oil to cope in the event of a fire. The problems discussed in this study include among others the design of the installation of Foam Chamber to protect Crude Palm Oil storage. Then calculate the amount of water requirements, the number of foam needs and the pump capacity needed in the form of a manual calculation and the Pipe Flow Expert Software for comparison. After doing the final stage of the discussion is the estimated Material Cost needed. Crude Palm Oil storage has a surface area of ​​32 m2. Discharge time is 30 minutes with application rate maks 2,76 m3/min. Crude Palm Oil storage has 1 outlet discharge by laying 1 m (1 ft) above the surface of the storage rack. Outlet diameter of 3 inches, 2 inch inlet pipe. The amount of foam needs is 1653.12 liters and water is 53450.88 liters and pump power for the calculation of Pipe Flow Expert software is 23,41 Kw and manual calculation is 21,848 Kw. Obtained the value of the Estimated Cost of Material Costs of Rp.369,633,050, -